Inspection Status: Correction Required

Inspection History: VIOL - MEANS OF EGRESS

Date Description Inspector Results Comments
06/08/2009 VIOL - MEANS OF EGRESS Correction Required 1008.1.8.4 Bolt locks.
Manually operated flush bolts or surface bolts are not permitted.

_____ Remove the slide bolt from the ---- egress door, as bolt lock of any kind are not permitted

1011.5.3 Power source.
Exit signs shall be illuminated at all times. To ensure continued illumination for the duration of not less than 90 minutes in case of primary power loss, the sign illumination means shall be connected to an emergency power system provided from storage batteries, unit equipment or an on-site generator. The installation of the emergency power system shall be in accordance with Section 2702 of the International Building Code

_____Repair or replace exit signs.

Call Inspector Pursley at 235-4709 or 791-4502, if you have any further questions.