Case: T09FR01896

Parcel: 13321158E


Addresses:

6735 E BROADWAY BL

Inspection Status: Correction Required

Inspection History: VIOL - MEANS OF EGRESS

Date Description Inspector Results Comments
06/08/2009 VIOL - MEANS OF EGRESS Correction Required 1008.1.8 Door operations.
Except as specifically permitted by this section egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort.

_____ Remove the double-key lock and replace with an approved locking device such as, thumb turn lock or panic hardware

1008.1.8.3 Locks and latches.
Locks and latches shall be permitted to prevent operation of doors where any of the following exists…
-- 2. In buildings in occupancy Group A having an occupant load of 300 or less, Groups B, F, M and S, and in places of religious worship, the main exterior door or doors are permitted to be equipped with key-operated locking devices from the egress
side provided:
-- 2.1. The locking device is readily distinguishable as locked,
-- 2.2. A readily visible durable sign is posted on the egress side on or adjacent to the door stating: THIS DOOR TO REMAIN UNLOCKED WHEN BUILDING IS OCCUPIED. The sign shall be in letters 1 inch (25 mm) high on a contrasting background,
-- 2.3. The use of the key-operated locking device is revokable by the fire code official for due cause.





_____ Place the wording "THIS DOOR TO REMAIN UNLOCKED WHEN BUILDING IS OCCUPIED" visibly above your main
egress door

1011.5.3 Power source.
Exit signs shall be illuminated at all times. To ensure continued illumination for the duration of not less than 90 minutes in case of primary power loss, the sign illumination means shall be connected to an emergency power system provided from storage batteries, unit equipment or an on-site generator. The installation of the emergency power system shall be in accordance with Section 2702 of the International Building Code

_____Repair or replace exit signs.

Call Inspector Pursley at 235-4709 or 791-4502, if you have any further questions.
Thank you.

Re-inspection passed: _____________________ ___/___/___