Case: T09FR01887

Parcel: 13824022E


Addresses:

1825 W VALENCIA RD

Inspection Status: Violation

Inspection History: VIOL - MEANS OF EGRESS

Date Description Inspector Results Comments
06/08/2009 VIOL - MEANS OF EGRESS Violation 1003.6 - Means of egress continuity. The path of egress travel along a means of egress shall not be interrupted by any building element other than a means of egress component as specified in this chapter. Obstructions shall not be placed in the required width of a means of egress except projections permitted by this chapter. The required capacity of a means of egress system shall not be diminished along the path of egress travel.
_____ Clear exit path, and maintain it this way.
_____ Provide copy of approved plans for enclosure of patio on NE patr of the building.
06/08/2009 VIOL - MEANS OF EGRESS Violation 1008.1.8 Door operations. Except as specifically permitted by this section egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort.
____Remove locking mechanism from kitchen emergency exit door.
____Remove sliding bolts from E side emergency exit.
06/08/2009 VIOL - MEANS OF EGRESS Violation 1011.2 - Illumination. Exit signs shall be internally or externally illuminated.
_____ Repair/replace exit signs