Case: T09FR01870

Parcel: 13321074A


Addresses:

6355 E BROADWAY BL


Inspection Status: Correction Required

Inspection History: VIOL - MEANS OF EGRESS

Case Number - T09FR01870

Inspection Description - VIOL - MEANS OF EGRESS

Inspection Status - Correction Required

Date Description Inspector Results Comments
06/04/2009 VIOL - MEANS OF EGRESS Correction Required 1008.1.8 Door operations.
Except as specifically permitted by this section egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort.

_____ Remove the double-key lock and replace with an approved locking device such as, thumb turn lock or panic hardware


Call Inspector Pursley at 235-4709 or 791-4502, if you have any further questions.
Thank you.

Re-inspection passed: _____________________ ___/___/___