Case: T09FR01870

Parcel: 13321074A


Addresses:

6355 E BROADWAY BL


Inspection Status: Correction Required

Inspection History: VIOL - BUILDING SVCS & SYSTEMS

Case Number - T09FR01870

Inspection Description - VIOL - BUILDING SVCS & SYSTEMS

Inspection Status - Correction Required

Date Description Inspector Results Comments
06/04/2009 VIOL - BUILDING SVCS & SYSTEMS Correction Required 605.1 Abatement of electrical hazards.
Identified electrical hazards shall be abated. Identified hazardous electrical conditions in permanent wiring shall be brought to the attention of the code official responsible for enforcement of the ICC Electrical Code. Electrical wiring, devices, appliances and other equipment that is modified or damaged and constitutes an electrical shock or fire hazard shall not be used…

_____ Remove locks on breakers in your electrical panel


605.4.2 Power supply
Relocatable power taps shall be directly connected to a permanently installed receptacle.

____Remove daisy-chained multi-plug adapters.






605.5 Extension cords
Extension cords and flexible cords shall not be a substitute for permanent wiring. Cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact. Extension cords shall be used only with portable appliances.

_____ All extension cords shall be removed and/or replace with approved fused power strips.