Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: INSP - FULL
Case Number - T09FR01839
Inspection Description - INSP - FULL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/22/2009 | INSP - FULL | Approved | hydro test done on system. System ok. | |
| 06/26/2009 | INSP - FULL | Violation | 1). ). the kitchen hood extinguishing system has a non compliance tag indicating non compliance with the fire code, indicating hydrostatic testing is required for agent container bottle. To complete compliance a new Commercial Kitchen System Report must be submitted without deficiencies. Report may be faxed to E. Griffin at 520-791-5346 This letter is to inform you that abatement of these Tucson Fire Code violations must be completed by July 9, 2009 . A re-inspection shall be conducted at that time to ensure compliance. Failure to comply with these Tucson Fire Code requirements could result in civil litigation under; City of Tucson Ordinance 9609. |
|
| 06/10/2009 | INSP - FULL | Violation | 1). the kitchen hood extinguishing g system has a non compliance tag indicating non compliance with the fire code. This is violation of The International Fire Code 2006 which states: 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Nonrequired fire protection systems and equipment shall be inspected, tested and maintained or removed. Currently the tag indicated that this system is not being maintained. This system shall be maintained.. |