Case: T09FR01792

Parcel: 133291840


Addresses:

8455 E BROADWAY BL

Inspection Status: Approved

Inspection History: VIOL - MEANS OF EGRESS

Date Description Inspector Results Comments
07/06/2009 VIOL - MEANS OF EGRESS Approved
05/26/2009 VIOL - MEANS OF EGRESS Violation Double keyed lock on door:
1008.1.8 Door operations. Except as specifically permitted by this section egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort.

______ Remove Keyed dead bolts. [except front door.] Thumb turn type ok except in panic hardware door.Panic Hardware:

TFC2006 / 1028.8 [Tucson Fire Code Modifications] Where panic hardware and fire exit hardware is installed, whether required or not, panic or fire exit hardware shall be the only locking device on the door except where otherwise permitted in this code.
05/26/2009 VIOL - MEANS OF EGRESS Violation Exit signs not lit:

TFC 1026.3 Exit sign illumination. Exit signs shall be internally or externally illuminated.

_____Fix light in exit signs.
05/26/2009 VIOL - MEANS OF EGRESS Violation Emergency lighting:

IFC2006 [with modifications]/ 1006.3 Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premise's electrical supply. In the event of power supply failure, an emergency electrical system shall automatically illuminate the following areas: [where currently located]

______Fix all inoperative emergency lights.