Case: T09FR01792

Parcel: 133291840


Addresses:

8455 E BROADWAY BL

Inspection Status: Approved

Inspection History: VIOL - BUILDING SVCS & SYSTEMS

Date Description Inspector Results Comments
07/06/2009 VIOL - BUILDING SVCS & SYSTEMS Approved
05/26/2009 VIOL - BUILDING SVCS & SYSTEMS Violation Open wire boxes/ splices:

TFC2006 605.6 Unapproved conditions. Open junction boxes and open-wiring splices shall be prohibited. Approved covers shall be provided for all switch and electrical outlet boxes.

______Cover wires in an approved manner. [switchcovers and outlet covers in front office area, showroom and sw corner of shop]
05/26/2009 VIOL - BUILDING SVCS & SYSTEMS Violation Extension cords:

TFC2006/ 605.5 Extension cords. Extension cords and flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact. Extension cords shall be used only with portable appliances.

_____Replace with approved fused power strip - or remove.
05/26/2009 VIOL - BUILDING SVCS & SYSTEMS Violation Blocked electrical panel:

TFC 605.3 Working space and clearance. A working space of not less than 30 inches (762 mm) in width, 36 inches (914 mm) in depth and 78 inches (1981 mm) in height shall be provided in front of electrical service equipment.

______Clear area in front of electrical panel in an approved manner.