Case: T09FR01790

Parcel: 12511055A


Addresses:

1001 N ALVERNON WY

Inspection Status: Approved

Inspection History: INSP - FULL

Date Description Inspector Results Comments
07/24/2009 INSP - FULL Approved CONTRACTORS REPORT TO SYSTEMS
07/07/2009 INSP - FULL Correction Required DURING THE ANNUAL INSPECTION THE FOLLOWING DEFICIENCIES WERE FOUND AND SHALL BE CORRECTED WITHIN 30 DAYS. A COPY OF THE REVISED INSPECTION TO BE SENT TO THIS OFFICE.

1) THE CONTROL VALVE AND MAIN DRAIN REQUIRE READABLE SIGNAGE.

2) PRESSURE GUAGES SHALL BE REPLACED OR CALIBRATED

3) THE INTERNAL VALVE INSPECTION IS DUE.
07/01/2009 INSP - FULL Correction Required SECOND NOTICE
THIS OFFICE HAS NOT RECEIVED A REPORT OF COMPLIANCE FOR THE NOTICE DATED 5-26-09, FOR THE ABOVE LISTED DEFICIENCY CONCERNING THE FIRE PROTECTION SYSTEM AT 1001 N. ALVERNON. IF CORRECTED HAVE THE CONTRACTOR OF RECORD FORWARD THEIR REPORT.
05/26/2009 INSP - FULL Correction Required FIRE PROTECTION SYSTEMS ARE REQUIRED TO BE INSPECTED AND TESTED ON AN ANNUAL BASIS. THE LAST REPORT OF COMPLIANCE THE FIRE PREVENTION OFFICE HAS RECEIVED IS DATED 4-30-03. PLEASE PROVIDE THIS OFFICE WITH A CURRENT REPORT WITH IN 30 DAYS. IF COMPLETED WITHIN THE LAST YEAR, HAVE THE CONTRACTOR OF RECORD FORWARD A COPY OF THEIR INSPECTION.