Case: T09FR01780

Parcel: 12709011M


Addresses:

335 N WILMOT RD


Inspection Status: Approved

Inspection History: INSP - REINSPECTION

Case Number - T09FR01780

Inspection Description - INSP - REINSPECTION

Inspection Status - Approved

Date Description Inspector Results Comments
08/04/2009 INSP - REINSPECTION Approved reports delivered to systems engineering
06/16/2009 INSP - REINSPECTION Violation 335 North Wilmot
1). Fire sprinkler test and inspection report shall be submitted. IFC 901.6
2)..Frill drill date has been set for October7th, 2009 at 10 AM.
3). Vending machines must e removed .
Currently vending machines are in exit passageway. This is in violation of the following fire requirements;
4).. Fire alarm test report shall be submitted. IFC 901.6