Inspection History Details
Inspection Status: Approved
Inspection History: INSP - FULL
Case Number - T09FR01780
Inspection Description - INSP - FULL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/04/2009 | INSP - FULL | Approved | ||
05/22/2009 | INSP - FULL | Violation | 1). currently there is combustible material in electrical rooms. All shall e removed. IFC 315.2.3 2).Suite 400. Remove material from top shelf. It is blocking sprinkler flow. IFC 903.3 3). Vault; 1st floor. Remove excessive combustible material. 4). 1st floor. Remove all plastic hangings from ceiling tiles. Immediately. This material is very flammable. IFC 703.3 5).Fire drill required. Date shall be determined by 6-4-09. |