Case: T09FR01780

Parcel: 12709011M


Addresses:

335 N WILMOT RD


Inspection Status: Approved

Inspection History: INSP - FULL

Case Number - T09FR01780

Inspection Description - INSP - FULL

Inspection Status - Approved

Date Description Inspector Results Comments
08/04/2009 INSP - FULL Approved
05/22/2009 INSP - FULL Violation 1). currently there is combustible material in electrical rooms. All shall e removed. IFC 315.2.3
2).Suite 400. Remove material from top shelf. It is blocking sprinkler flow. IFC 903.3
3). Vault; 1st floor. Remove excessive combustible material.
4). 1st floor. Remove all plastic hangings from ceiling tiles. Immediately. This material is very flammable. IFC 703.3
5).Fire drill required. Date shall be determined by 6-4-09.