Case: T09FR01744

Parcel: 11703180A


Addresses:

325 W 2ND ST

Inspection Status: Correction Required

Inspection History: INSP - FULL

Date Description Inspector Results Comments
07/21/2009 INSP - FULL Correction Required DELIVERED AN APPEAL NOTICE TO MR. LANDER OF THR DUNBAR ASSOCIATION
07/06/2009 INSP - FULL Correction Required DURING THE ANNUAL SPRINKLER INSPECTION THE FOLLOWING DEFICIENCIES WERE FOUND, PLEASE PROVIDE A CORRECTION REPORT WITHIN 30 DAYS.

1) PRESSURE GUAGES SHALL BE RECALIBRATED OR CHANGED OUT

2) PROVIDE AN INSPECTORS TEST VALVE

3) PROVIDE A 5 YEAR INTERNAL VALVE INSPECTION
06/22/2009 INSP - FULL Correction Required SECOND NOTICE
THIS OFFICE HAS NOT RECEIVED A REPORT OF COMPLIANCE FOR THE NOTICE DATED 5-18-09, FOR THE ABOVE LISTED DEFICIENCY CONCERNING THE FIRE PROTECTION SYSTEM AT 325 W. SECOND. IF CORRECTED PLEASE FORWARD A REPORT OF INSPECTION
05/18/2009 INSP - FULL Correction Required FIRE PROTECTION SYSTEMS ARE REQUIRED TO BE INSPECTED AND TESTED ON AN ANNUAL BASIS. WHEREAS THIS OFFICE HAS NOT RECEIVED A REPORT OF COMPLIANCE SINCE 2002, PLEASE FORWARD TO THIS OFFICE WITH IN 30 DAYS A CURRENT REPORT OF INSPECTION, PERFORMED BY A LICENSED CONTRACTOR.