Case: T09FR01698

Parcel: 11505087D


Addresses:

333 W GRANT RD


Inspection Status: Approved

Inspection History: INSP - FULL

Case Number - T09FR01698

Inspection Description - INSP - FULL

Inspection Status - Approved

Date Description Inspector Results Comments
05/14/2009 INSP - FULL Approved Repairs made
03/31/2009 INSP - FULL Correction Required 1011.4 Internally illuminated exit signs. Internally illuminated exit signs shall be listed and labeled and shall be installed in accordance with the manufacturer's instructions and Section 2702 of the International Building Code. Exit signs shall be illuminated at all times.

" The exit sign in on the rear door is not working. Please repair or replace the sign to ensure it is lit at all times and has a minimum of a 90 minute back up power source.


906.6 Unobstructed and unobscured. Portable fire extinguishers shall not be obstructed or obscured from view. In rooms or areas in which visual obstruction cannot be completely avoided, means shall be provided to indicate the locations of extinguishers.

" Unblock the extinguisher by the front door. All extinguishers shall have a current tag stating they have been tested annually.


605.6 Unapproved conditions. Open junction boxes and open-wiring splices shall be prohibited. Approved covers shall be provided for all switch and electrical outlet boxes.

" Replace the cover on the outlet box.




1006.3 Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premises' electrical supply. In the event of power supply failure, an emergency electrical system shall automatically illuminate.

The emergency power system shall provide power for a duration of not less than 90 minutes and shall consist of storage batteries, unit equipment or an on-site generator. The installation of the emergency power system shall be in accordance with Section 2702 of the International Building Code.

" Repair the emergency light.