Case: T09FR01606

Parcel: 12704245A


Addresses:

5033 E 5TH ST


Inspection Status: Violation

Inspection History: VIOL - MEANS OF EGRESS

Case Number - T09FR01606

Inspection Description - VIOL - MEANS OF EGRESS

Inspection Status - Violation

Date Description Inspector Results Comments
05/12/2009 VIOL - MEANS OF EGRESS Violation IFC.1008.1.8.3 Locks and latches.
Locks and latches shall be permitted to prevent operation of doors where any of the following exists:....
2.2. A readily visible durable sign is posted on the egress side on or adjacent to the door stating: THIS DOOR TO REMAIN UNLOCKED WHEN BUILDING IS OCCUPIED. The sign shall be in letters 1 inch (25 mm) high on a contrasting background,

____Sign required on front door as stated in above code: "THIS DOOR TO REMAIN UNLOCKED WHEN BUILDING IS OCCUPIED".

IFC.1008.1.8.4 Bolt locks.
Manually operated flush bolts or surface bolts are not permitted.

____ Remove flush bolts from rear door.