Case: T09FR01589

Parcel: 12405050A


Addresses:

874 E UNIVERSITY BL


Inspection Status: Violation

Inspection History: VIOL - FIRE PROTECTION SYSTEMS

Case Number - T09FR01589

Inspection Description - VIOL - FIRE PROTECTION SYSTEMS

Inspection Status - Violation

Date Description Inspector Results Comments
05/11/2009 VIOL - FIRE PROTECTION SYSTEMS Violation 904.1 General. Automatic fire-extinguishing systems, other
than automatic sprinkler systems, shall be designed, installed,
inspected, tested and maintained in accordance with the provisions
of this section and the applicable referenced standards.

____Repair all deficiencies noted in Cintas Fire Supression Inspection Report.
05/11/2009 VIOL - FIRE PROTECTION SYSTEMS Violation 904.11.6.3 Cleaning. Hoods, grease-removal devices,
fans, ducts and other appurtenances shall be cleaned at
intervals necessary to prevent the accumulation of
grease. Cleanings shall be recorded, and records shall
state the extent, time and date of cleaning. Such records
shall be maintained on the premises.

____Hood/Ducts need to be cleaned. Provide documentation.
05/11/2009 VIOL - FIRE PROTECTION SYSTEMS Violation 904.11.2 System interconnection. The actuation of the fire
extinguishing system shall automatically shut down the fuel
or electrical power supply to the cooking equipment. The
fuel and electrical supply reset shall be manual.

____Electric under the hood needs to shut off when system is tripped.
05/11/2009 VIOL - FIRE PROTECTION SYSTEMS Violation 904.2.1 Commercial hood and duct systems. Each
required commercial kitchen exhaust hood and duct system
shall be protected with an approved automatic fire-extinguishing system installed in accordance with this code.

[M] 609.1 General. Commercial kitchen exhaust hoods shall
comply with the requirements of the International Mechanical
Code.
[M] 609.2 Where required.AType I hood shall be installed at
or above all commercial cooking appliances and domestic
cooking appliances used for commercial purposes that produce
grease vapors.

____Current appliances (pizza oven) do not have proper hood coverage or nozzle protection.