Case: T09FR01581

Parcel: 10409002D


Addresses:

475 W WETMORE RD


Inspection Status: Correction Required

Inspection History: VIOL - MEANS OF EGRESS

Case Number - T09FR01581

Inspection Description - VIOL - MEANS OF EGRESS

Inspection Status - Correction Required

Date Description Inspector Results Comments
05/08/2009 VIOL - MEANS OF EGRESS Correction Required IFC 1027.5 Illumination emergency power. The power supply for
means of egress illumination shall normally be provided by the
premises’ electrical supply. In the event of power supply failure,
illumination shall be automatically provided from an
emergency system...

_____1. Test all emergency lighting units and EXIT signs for emergency back-up power. Repair any deficiencies and provide documentation of the repairs needed.
05/08/2009 VIOL - MEANS OF EGRESS Correction Required IFC 1008.1.8 Door operations. Except as specifically permitted
by this section egress doors shall be readily openable from
the egress side without the use of a key or special knowledge
or effort.

_____1. Remove the chain and padlock from the 200's EXIT door.