Case: T09FR01581

Parcel: 10409002D


Addresses:

475 W WETMORE RD


Inspection Status: Correction Required

Inspection History: VIOL - FIRE PROTECTION SYSTEMS

Case Number - T09FR01581

Inspection Description - VIOL - FIRE PROTECTION SYSTEMS

Inspection Status - Correction Required

Date Description Inspector Results Comments
05/08/2009 VIOL - FIRE PROTECTION SYSTEMS Correction Required IFC 904.11.6.3 Cleaning. Hoods, grease-removal devices,
fans, ducts and other appurtenances shall be cleaned at
intervals necessary to prevent the accumulation of
grease. Cleanings shall be recorded, and records shall
state the extent, time and date of cleaning. Such records
shall be maintained on the premises.

_____1. Clean and remove all grease accumulation from the kitchen hood system and provide documentation of the cleaning.
05/08/2009 VIOL - FIRE PROTECTION SYSTEMS Correction Required IFC 901.6 Inspection, testing and maintenance. Fire detection,
alarm and extinguishing systems shall be maintained in an
operative condition at all times, and shall be replaced or
repaired where defective.

_____1. Service and tag the automatic sprinkler system.