Case: T09FR01573

Parcel: 110120960


Addresses:

5301 E GRANT RD


Inspection Status: Approved

Inspection History: INSP - FULL

Case Number - T09FR01573

Inspection Description - INSP - FULL

Inspection Status - Approved

Date Description Inspector Results Comments
07/23/2009 INSP - FULL Approved ALL NOTED TFC VIOLATONS HAVE BEEN CORRECTED.
05/07/2009 INSP - FULL Violation 1.) TFC 901.6 IN AHCCCS OFFICE A SPRINKLER HEAD ESCUTHEON IS MISSING IN THE OFFICE SUPPLY CLOSET.
05/07/2009 INSP - FULL Violation 2.) TFC 703.1.1 IN G.I. LAB EMPLOYEE BREAK ROOM THE WALL PENETRATION ABOVE THE COUNTER TOP MUST BE SEALED.
05/07/2009 INSP - FULL Violation 3.) TFC 703.1.1 IN TANKERSLY COMPUTER LEARNING LAB THE BROKEN CEILING TILE AND WATER DAMAGED CEILING TILE MUST BE REPLACED.
05/07/2009 INSP - FULL Violation 4.) TFC 904.5.1 IN KITCHEN AREA THE "GRILL" IS PAST DUE FOR 6 MO. INSPECTION.
05/07/2009 INSP - FULL Violation 5.) TFC 901.6 IN DAIRY PRODUCTS WALK-IN FREEZER THE REAR SPRINKLER HEAD IS MISSING THE ESCUTCHEON PLATE AND ADDITIONAL INSULATION AROUND THE PIPING IS REQUIRED.
05/07/2009 INSP - FULL Violation 6.) TFC 901.6 THE SPRINKLER HEAD JUST OUTSIDE OF THE DAIRY PROD. WALK-IN FREEZER IS MISSING AN ESCUTCHEON.
05/07/2009 INSP - FULL Violation 7.) TFC 3003.5.3 TWO COMPRESSED GAS CYLINDERS IN KITCHEN E.S. ROOM ARE NOT SECURED TO PREVENT FALLING.
05/07/2009 INSP - FULL Violation 8.) TFC 3003.5.3 IN CO2 CYLINDER ROOM LARGE "K" SIZE CYLINDER IS NOT SECURED AND TWO SMALL CO2 CYLINDERS ARE NOT SECURED TO PREVENT FALLING.
05/07/2009 INSP - FULL Violation 9.) TFC 901.6 IN FOOD SERVICES DIRECTOR'S OFFICE THE HVAC VENT COVER MUST BE SECURED TO THE CEILING TO SEAL GAP.