Inspection Status: Correction Required

Inspection History: VIOL - FIRE PROTECTION SYSTEMS

Case Number - T09FR01563

Inspection Description - VIOL - FIRE PROTECTION SYSTEMS

Inspection Status - Correction Required

Date Description Inspector Results Comments
05/06/2009 VIOL - FIRE PROTECTION SYSTEMS Correction Required IFC 901.6 Inspection, testing and maintenance. Fire detection,
alarm and extinguishing systems shall be maintained in an
operative condition at all times, and shall be replaced or
repaired where defective.

_____1. Service and tag the portable fire extinguisher.
05/06/2009 VIOL - FIRE PROTECTION SYSTEMS Correction Required IFC 906.9 Height above floor. Portable fire extinguishers having a
gross weight not exceeding 40 pounds (18 kg) shall be installed
so that its top is not more than 5 feet (1524 mm) above the floor.

_____1. The portable fire extinguisher shall be lowered so that its top is not more than 5 feet (1524 mm) above the floor.


________________________________________________
(John E. Bieg, Fire Inspector, Tucson Fire Department)


I, ______________________ have received a copy of this inspection report. (Building Representative)


______________________________
(Captain)


Re-inspection scheduled on or after _____/_____/_____
Call Inspector Bieg at 235-4785 or 791-4502, if you have any further questions.


All noted Tucson Fire Code violations have been corrected: _____/_____/_____