Case: T09FR01549

Parcel: 12415008A


Addresses:

827 E 17TH ST


Inspection Status: Approved

Inspection History: VIOL - FIRE PROTECTION SYSTEMS

Case Number - T09FR01549

Inspection Description - VIOL - FIRE PROTECTION SYSTEMS

Inspection Status - Approved

Date Description Inspector Results Comments
06/17/2009 VIOL - FIRE PROTECTION SYSTEMS Approved All discrepancies corrected and sprinkler system serviced 5/24/2009; in FULL COMPLIANCE.
05/06/2009 VIOL - FIRE PROTECTION SYSTEMS Correction Required Records indicate that the fire sprinkler system is overdue its annual inspection / servicing.
05/06/2009 VIOL - FIRE PROTECTION SYSTEMS Correction Required A full inspection was conducted with the following discrepancies noted:
1.The Automatic Fire Sprinklers System is overdue its annual testing/servicing, therefore not in full compliance. Have an annual inspection / serving of your sprinkler system. INTERNATIONAL FIRE CODE (IFC) 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be serviced annually and maintained in an operative condition at all times, and shall be replaced or repaired where defective.

2. There are two areas within the office that require to be fire sealed where pipes penetrate the ceiling leaving an avenue for smoke and fire to travel. Fire seal the openings. INTERNATIONAL FIRE CODE (IFC) 703.1 Openings made therein for the passage of pipes, electrical conduit,wires, ducts, air transfer openings and holes made for any reason shall be protected with approved methods capable of resisting the passage of smoke and fire.

A Report of Occupancy Inspection was issued with a 6/04/2009 suspense.

Note: A Certificate of Occupancy (C of O) was not available at time of inspection.