Case: T09FR01537

Parcel: 133233570


Addresses:

7671 E BROADWAY BL


Inspection Status: Approved

Inspection History: VIOL - FIRE PROTECTION SYSTEMS

Case Number - T09FR01537

Inspection Description - VIOL - FIRE PROTECTION SYSTEMS

Inspection Status - Approved

Date Description Inspector Results Comments
06/24/2009 VIOL - FIRE PROTECTION SYSTEMS Approved
05/05/2009 VIOL - FIRE PROTECTION SYSTEMS Violation Extinguishers not tagged / inspected:

TFC2006/ 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Nonrequired fire protection systems and equipment shall be inspected, tested and maintained or removed.

______ Extinguishers shall be maintained, inspected and tagged [annually] in accordance with this code.
05/05/2009 VIOL - FIRE PROTECTION SYSTEMS Violation Unsupervised Main Valve:
907.20.5 Maintenance, inspection and testing. The building
owner shall be responsible for ensuring that the fire and
life safety systems are maintained in an operable condition
at all times. Service personnel shall meet the qualification
requirements of NFPA 72 for maintaining, inspecting and
testing such systems. A written record shall be maintained
and shall be made available to the fire code official.

______ Chain main valve open or have valve electronically supervised.
05/05/2009 VIOL - FIRE PROTECTION SYSTEMS Violation Sprinkler system:
903.5 Testing and maintenance. Sprinkler systems shall be tested and maintained in accordance with Section 901.

_______ System to be tested, and tagged annually.