Case: T09FR01506

Parcel: 10816008B


Addresses:

4980 N 1ST AV

Inspection Status: Approved

Inspection History: INSP - FULL

Date Description Inspector Results Comments
06/10/2009 INSP - FULL Approved INSPECTION REPORT TO SYSTEMS
06/01/2009 INSP - FULL Correction Required SECOND NOTIC
THIS OFFICE HAS NOT RECEIVED A REPORT OF COMPLIANCE FOR THE NOTICE DATED 4-30-09, FOR THE ABOVE LISTED DEFICIENCY CONCERNING THE FIRE PROTECTION SYSTEM AT 4980 N. 1ST. AVE. IF CORRECTED, HAVE THE CONTRACTOR OF RECORD FORWARD THEIR REPORT.
04/30/2009 INSP - FULL Correction Required FIRE PROTECTION SYSTEMS, SPRINKLERS AND ALARMS, ARE REQUIRED TO BE INSPECTED AND TESTED ON AN ANNUAL BASIS. THE LAST REPORT RECEIVED BY THIS OFFICE IS DATED 4-18-2007. pLEASE FORWARD WITHIN 30 DAYS A CURRENT REPORT OF INSPECTION.