Case: T09FR01473

Parcel: 13002003A


Addresses:

3030 E 22ND ST


Inspection Status: Violation

Inspection History: INSP - FULL

Case Number - T09FR01473

Inspection Description - INSP - FULL

Inspection Status - Violation

Date Description Inspector Results Comments
08/19/2009 INSP - FULL Violation 605.4 Multiplug adapters. Multiplug adapters, such as cube
adapters, unfused plug strips or any other device not complying
with the ICC Electrical Code shall be prohibited.
605.4.1 Power tap design. Relocatable power taps shall be
of the polarized or grounded type, equipped with
overcurrent protection, and shall be listed in accordance
with UL 1363.
605.4.2 Power supply. Relocatable power taps shall be
directly connected to a permanently installed receptacle.
605.4.3 Installation. Relocatable power tap cords shall not
extend through walls, ceilings, floors, under doors or floor
coverings, or be subject to environmental or physical damage.
605.5 Extension cords. Extension cords and flexible cords
shall not be a substitute for permanent wiring. Extension cords
and flexible cords shall not be affixed to structures, extended
through walls, ceilings or floors, or under doors or floor coverings,
nor shall such cords be subject to environmental damage
or physical impact. Extension cords shall be used only with
portable appliances.
Do not use extension cord for perminant wiring.
08/19/2009 INSP - FULL Violation 703.1 Maintenance. The required fire-resistance rating of
fire-resistance-rated construction (including walls, firestops,
shaft enclosures, partitions, smoke barriers, floors, fire-resistive
coatings and sprayed fire-resistant materials applied to
structural members and fire-resistant joint systems) shall be
maintained. Such elements shall be properly repaired, restored
or replaced when damaged, altered, breached or penetrated.
Openings made therein for the passage of pipes, electrical conduit,
wires, ducts, air transfer openings and holes made for any
reason shall be protected with approved methods capable of
resisting the passage of smoke and fire. Openings through
fire-resistance-rated assemblies shall be protected by self- or
automatic-closing doors of approved construction meeting the
fire protection requirements for the assembly.
Fix all holes.
08/19/2009 INSP - FULL Violation 315.2 Storage in buildings. Storage of combustible materials
in buildings shall be orderly. Storage shall be separated from
heaters or heating devices by distance or shielding so that ignition
cannot occur.
315.2.1 Ceiling clearance. Storage shall be maintained 2
feet (610 mm) or more below the ceiling in nonsprinklered
areas of buildings or a minimum of 18 inches (457 mm)
below sprinkler head deflectors in sprinklered areas of
buildings.
Do not store combustible materials next to Hot Water heater.
08/19/2009 INSP - FULL Violation 1008.1.8 Door operations. Except as specifically permitted
by this section egress doors shall be readily openable from
the egress side without the use of a key or special knowledge
or effort.
1008.1.8.1 Hardware. Door handles, pulls, latches,
locks and other operating devices on doors required to be
accessible by Chapter 11 of the International Building
Code shall not require tight grasping, tight pinching or
twisting of the wrist to operate.
Remove existing latches, locks and any hardware that will not allow the door to open. Panic hardware would be appropriate.