Inspection History Details
Inspection Status: Correction Required
Inspection History: INSP - FULL
Case Number - T09FR01434
Inspection Description - INSP - FULL
Inspection Status - Correction Required
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/24/2009 | INSP - FULL | Correction Required | DURING THE ANNUAL SPRINKLER INSPECTION THE FOLLOWING DEFICIENCY WAS FOUND AND SHALL BE REPAIRED WITH IN 30 DAYS. A COPY OF A REPAIR ORDER SHALL BE FORWARDED TO THIS OFFICE 1) A HYDRAULIC CALCULATION PLATE SHALL BE AT THE RISER 2) A SPARE HEAD BOX WITH THE COMPLIMENT OF THE CORRECT SPRINKLERS AND THE SPECIAL WRENCH SHALL BE PROVIDED. IT MAY BE HUNG INSIDE THE FRONT DOOR. 3) ALL EMERGENCY AND EXITLIGHTS SHALL BE IN REPAIR |