| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/09/2009 | INSP - FULL | Approved | CONTRACTORS REPORT AND REPAIR INVOICE TO SYSYEMS | |
| 06/12/2009 | INSP - FULL | Correction Required | SECOND NOTICE THIS OFFICE HAS NOT RECEIVED A REPORT OF COMPLIANCE FOR THE NOTICE DATED 4-23-09, FOR THE ABOVE LISTED DEFICIENCIES CONCERNING THE FIRE PROTECTION SYSTEM AT 1443 E. BLACKLIDGE. IF CORRECTED HAVE THE CONTRACTOR OF RECORD FORWARD THEIR REPORT. |
|
| 04/23/2009 | INSP - FULL | Correction Required | DURING THE ANNUAL SPRINKLER INSPECTION THE FOLLOWING DEFICIENCY WAS FOUND AND SHALL BE CORRECTED WITHIN 30 DAYS. 1) THE GUAGES ON THE SPRINKLER RISER ARE OVER 5 YEARS OLD, THEY SHALL BE REPLACED OR RE-CALIBRATED 2) 1 - 200 DEGREE, PENDANT, QUICK RESPONSE SPRINKLER HEAD SHALL BE ADDED TO THE SPARE HEAD BOX |