Inspection History Details
Inspection Status: Approved
Inspection History: INSP - FULL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/23/2009 | INSP - FULL | Approved | Petition of appeal to the Fire Code Official- re: No deadbolt locks may be used on a door separating back room from service area. Appeal- The service area is not enclosed and this door is not the only exit from service area, The deadbolt are need only on one side of door to keep back room secure after closing. The door remains open during business hours. Appeal approved by Chief Dan Uthe. |