Case: T09FR01389

Parcel: 107083200


Addresses:

728 W GRANT RD


Inspection Status: Approved

Inspection History: INSP - FULL

Case Number - T09FR01389

Inspection Description - INSP - FULL

Inspection Status - Approved

Date Description Inspector Results Comments
06/01/2009 INSP - FULL Approved REPAIR INVOICE WAS SENT TO SYSTEMS BY CONTRACTOR
05/28/2009 INSP - FULL Correction Required DURING THE ANNUAL SPRINKLER INSPECTION THE FOLLOWING DEFICIENCY WAS FOUND AND SHALL BE REPAIRED WITHIN 30 DAYS. PLEASE FORWARD THIS INSPECTOR A COPY OF THE REPAIR MANIFEST.

1) THE TOP GUAGE AT THE SPRINKLER RISER WAS INOPERATIVE AND SHALL BE REPLACED

2) THE INSPECTORS TEST VALVE IS CORRODED SHUT AND SHALL BE REPLACED
04/23/2009 INSP - FULL Correction Required 901.6 FIRE PROTECTION SYSTEMS ARE REQUIRED TO BE INSPECTED AND TESTED ON AN ANNUAL BASIS. WHEREAS THIS OFFICE HAS NOT RECEIVED A COPY OF THE REQUIRED INSPECTION SINCE 2006, PLEASE HAVE THE INSPECTING SPRINKLER CONTRACTOR FORWARD THEIR REPORT WITHIN 30 DAYS.