Case: T09FR01381

Parcel: 125080820


Addresses:

105 N NORTON AV


Inspection Status: Violation

Inspection History: VIOL - MEANS OF EGRESS

Case Number - T09FR01381

Inspection Description - VIOL - MEANS OF EGRESS

Inspection Status - Violation

Date Description Inspector Results Comments
04/27/2009 VIOL - MEANS OF EGRESS Violation 1027.3 Exit sign illumination.
Exit signs shall be internally or externally illuminated. The face of an exit sign illuminated from an external source, shall have an intensity of not less than 5 foot-candles (54 lux). Internally illuminated signs shall provide equivalent luminance and be listed for the purpose.

____Exit sign in Primary Room must be serviced repaired.
04/22/2009 VIOL - MEANS OF EGRESS Violation 1028.3 Obstructions.
A means of egress shall be free from obstructions

____Remove all obstructions/tables from all exit corridors.
04/22/2009 VIOL - MEANS OF EGRESS Violation 1027.5 Illumination emergency power.
The power supply for means of egress illumination shall normally be provided by the premises’ electrical supply. In the event of power supply failure, illumination shall be automatically provided from an emergency system for the following occupancies where such occupancies require two or more means of egress:
1. Group A having 50 or more occupants.
Exception: Assembly occupancies used exclusively as a place of worship and having an occupant load of less than 300....

____Emergency lighting in Clerks Office shall be serviced/repaired.
____Emergency lighting required in Rostrum, Chapel and Cultural Hall.
04/22/2009 VIOL - MEANS OF EGRESS Violation 1008.1 Doors.
Means of egress doors shall meet the requirements of this section. Doors serving a means of egress system shall meet the requirements of this section and Section 1017.2. Doors provided for egress purposes in numbers greater than required by this code shall meet the requirements of this section.

1008.1.8 Door operations.
Except as specifically permitted by this section egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort.

____Key lock needs to be removed from Room 209 and Primary Room.
____ Egress doors in Basketball Court must operate properly from the egress side without the use of a key or any special knowledge.