Inspection Status: Approved
Inspection History: INSP - FULL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/12/2009 | INSP - FULL | Approved | APPROVED AS PER FIELD INSPECTION, SPRINKLER SYSTEM IS STAND ALONE FOR ONE BUILDING. THERE IS NOT A FIRE ALARM SYSTEM WITH A PANEL ON SITE. FIRE ALARM CONSISTS OF SINGLE STATION DETECTORS AND A HARD WIRED SMOKE TO ACTIVATE AN OUTSIDE FLASHING LIGHT. | |
| 04/20/2009 | INSP - FULL | Correction Required | DURING THE LAST ANNUAL SPRINKLER INSPECTION THE FOLLOWING DEFICIENCY WAS FOUND AND SHALL BE CORRECTED WITH IN 30 DAYS. A COPY OF THE REPAIR ORDER SHALL BE FFORWARDED TO THIS OFFICE 1) THE WATER FLOW AND TAMPER SHALL BE TIED INTO THE FIRE ALARM PANEL FOR NOTIFICATION |