Case: T09FR01303

Parcel: 11628001L

Inspection Status: Approved

Inspection History: INSP - FULL

Case Number - T09FR01303

Inspection Description - INSP - FULL

Inspection Status - Approved

Date Description Inspector Results Comments
07/02/2009 INSP - FULL Approved
05/15/2009 INSP - FULL Violation all systems, fire pump test submitted. delvered to systems
04/15/2009 INSP - FULL Violation On 4-9-09, a fire prevention inspection was conducted at The JW Marriott Starr Pass Resort and Spa, 3800 West Starr Pass Boulevard in Tucson, Arizona.

In attendance was Alvin Schultherie and Patrick Walker.

The following Tucson Fire Code Violation(s) was noted:

1). Fire alarm test report shall be submitted and all required repairs shall be completed. IFC 901.6
2). Fire pump test report shall be submitted and all required repairs shall be completed. IFC 913.5
3). Fire sprinkler and inspection report shall be submitted.. IFC 901.6
4). All internet rooms shall be provided with fire stopping, or all combustible materials shall be removed. IFC 703.1
5). All mechanical rooms shall be free from combustible materials. This includes all air handler rooms. IFC315.2.3
6).6th floor interment room blocked with plastic, please remove. IFC 515.2.3
7).6th room stairwell, remove all combustible materials. IFC 1028.2
8). All pool gates shall be self closing. IFC 111
9). Extend sprinkler coverage to room in parking garage. IFC 901.6

This letter is to inform you that abatement of these Tucson Fire Code violations must be completed by 5-7-09.
A re-inspection shall be conducted at that time to ensure compliance.

Thank for your cooperation with the fire department.
If you have questions, or if I may be of any assistance please call me at 791-4502 extension 127.