Inspection Status: Approved
Inspection History: INSP - FULL
| Date |
Description |
Inspector |
Results |
Comments |
| 08/31/2009 |
INSP - FULL |
|
Approved |
THE SPRINKLER SYSTEM DESIGN WAS APPROVED IN 1975. THE HEADS COULD NOT BE 50 YEARS OLD. APPROVED. 04/21/09 |
| 04/15/2009 |
INSP - FULL |
|
Violation |
TFC 901.6 SHOW PROOF THAT SPRINKLER HEADS ARE LESS THAN 50 YEARS OLD OR REPLACE SPRINKLER HEADS PER NFPA 25 SECTION 5.3.1.1.1. |