Case: T09FR01254

Parcel: 131010480


Addresses:

5070 E 22ND ST

Inspection Status: Violation

Inspection History: VIOL - MEANS OF EGRESS

Date Description Inspector Results Comments
04/14/2009 VIOL - MEANS OF EGRESS Violation TFC 1014.2 - Egress through intervening spaces.
Means of egress are not prohibited through adjoining or intervening rooms or spaces in a Group H, S or F occupancy when the adjoining or intervening rooms or spaces are the same or a lesser hazard occupancy group.
Egress shall not pass through kitchens, storage rooms, closets or spaces used for similar purposes.

_____ Remove EXIT sign above door leading from Salon to parts room.
04/09/2009 VIOL - MEANS OF EGRESS Violation TFC 1003.6 - Means of egress continuity.
... Obstructions shall not be placed in the required width of a means of egress... The required capacity of a means of egress system shall not be diminished along the path of egress travel.

_____ Clear exit door from storage garage.
04/09/2009 VIOL - MEANS OF EGRESS Violation TFC 1008.1.8 - Door operations.
Except as specifically permitted by this section egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort.

_____ replace double key deadbolt with thumbturn on North bldg, front door.

_____ Remove bar lock from North bldg, South door.