Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Case: T09FR01252

Parcel: 133231390

Inspection Status: Correction Required

Inspection History: VIOL - MEANS OF EGRESS

Case Number - T09FR01252

Inspection Description - VIOL - MEANS OF EGRESS

Inspection Status - Correction Required

Date Description Inspector Results Comments
04/14/2009 VIOL - MEANS OF EGRESS Correction Required 1006.3 Illumination emergency power.
The power supply for means of egress illumination shall normally be provided by the premises' electrical supply, in the event of power supply failure, an emergency electrical system shall automatically illuminate… The emergency power system shall provide power for a duration of not less than 90 minutes and shall consist of storage batteries, unit equipment or an on-site generator. The installation of the emergency power system shall be in accordance with Section 2702 of the International Building Code.

____Have or show proof of emergency lighting.

1008.1.8 Door operations.
Except as specifically permitted by this section egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort.

_____ Remove the double-key lock and replace with an approved locking device such as, thumb turn lock or panic hardware

1011.5.3 Power source.
Exit signs shall be illuminated at all times. To ensure continued illumination for the duration of not less than 90 minutes in case of primary power loss, the sign illumination means shall be connected to an emergency power system provided from storage batteries, unit equipment or an on-site generator. The installation of the emergency power system shall be in accordance with Section 2702 of the International Building Code

____Have exit sign tested/repaired.

Re-inspection scheduled on or after ___/___/___
Call Inspector Pursley at 235-4709 or 791-4502, if you have any further questions.
Thank you.

Re-inspection passed: _____