Case: T09FR01252

Parcel: 133231390

Inspection Status: Correction Required

Inspection History: VIOL - FIRE PROTECTION SYSTEMS

Case Number - T09FR01252

Inspection Description - VIOL - FIRE PROTECTION SYSTEMS

Inspection Status - Correction Required

Date Description Inspector Results Comments
04/14/2009 VIOL - FIRE PROTECTION SYSTEMS Correction Required 901.6 Inspection, testing and maintenance.
Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective.

Section 904.11.7 All deep-fat fryers shall be installed with at least a 16 inch (406 mm)
space between the fryer and surface flames of adjacent cooking appliances.
Exception:





1. Where a steel or tempered glass baffle plate is installed at a minimum 8 inches
(203 mm) in height between the fryer and surface flames of the adjacent cooking
appliance, the requirement for a 16 inch space shall not apply. Where the fryer
and the surface flames of the adjacent cooking appliance are at different
horizontal planes, the minimum height of 8 inches (203 mm) shall be measured
from the higher of the two.

____Have hood system checked for proper configuration and tested.