Case: T09FR01246

Parcel: 10610005C


Addresses:

2020 W PRINCE RD


Inspection Status: Approved

Inspection History: INSP - FULL

Case Number - T09FR01246

Inspection Description - INSP - FULL

Inspection Status - Approved

Date Description Inspector Results Comments
06/02/2009 INSP - FULL Approved CORRECTIONS COMPLETED, COPY TO SYSTEMS
04/14/2009 INSP - FULL Correction Required DURING THE ANNUAL FIRE PROTECTION SYSTEM INSPECTION THE FOLLOWING DEFICIENCY WAS FOUND AND SHALL BE CORRECTED WITH IN 30 DAYS. PLEASE HAVE THE CONTRACTOR OF RECORD FORWARD THEIR CORRECTION REPORT.

1) RISER # 3 - THE PRESSURE GUAGE IS IN NEED OF RECALIBRATION OR TO BE CHANGED OUT

2) RISER # 4 - THE PRESSURE GUAGE NEEDS TO BE RECALIBRATED OR CHANGED OUT. THE CONTROL VALVE ALSO NEEDS SIGNAGE

3) RISER # 5 - THE 1 1/2 " FIRE HOSE VALVES HAVE THE VALVES TURNED UPWARD AND PROTECTIVE CAPS ARE MISSING. THE HOSE VALVE AT COLUMN # 8 (N/W WAREHOUSE) HAS A BROKEN HANDLE THAT NEEDS TO BE REPLACED.

4) RISER # 6 - THE PRESSURE GUAGES NEED TO BE RECALIBRATED OR REPLACED.

5) RISER # 7 - THE GUAGES NEED TO BE RECALIBRATED OR REPLACED

6) RISER # 8 - PROVIDE SIGNAGE FOR THE CONTROL VALVE, PROVIDE THE CORRECT SPECIAL WRENCH FOR THE SPRINKLER HEADS INSTALLED, PRESSURE GUAGE SHALL BE RECALIBRATED OR REPLACED, THE TAMPER FLOW SWITCH DID NOT ANNUNCIATE AT THE ALARM PANEL, AT THIS ZONE THE ELECTRIC BELL DID NOT ANNUNCIATE AT THE ALARM PANEL.

7) RISER # 9 - PROVIDE SIGNAGE AT THE CONTROL VALVE, PROVIDE THE CORRECT SPECIAL WRENCH FOR THE SPRINKLER HEADS, PRESSURE GUAGES SHALL BE RECALIBRATED OR CHANGED OUT, SUPERVISORY SWITCH DID NOT ANNUNCIATE AT THE ALARM PANEL FOR THIS ZONE.