Inspection History Details
Inspection Status: Correction Required
Inspection History: INSP - FULL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/27/2009 | INSP - FULL | Correction Required | SECOND NOTICE THIS OFFICE HAS NOT RECEIVED A REPORT OF COMPLIANCE FOR THE NOTICE DATED 4-9-2009, FOR THE ABOVE LISTED DEFICIENCIES CONCERNING THE FIRE PROTECTION SYSTEM AT 1065 W. GRANT. IF CORRECTED HAVE THE CONTRACTOR OF RECORD FORWARD THEIR REPORT. |
|
| 04/09/2009 | INSP - FULL | Correction Required | DURING THE ANNUAL SPRINKLER INSPECTIONTHE FOLLOWING DEFICIENCY WAS FOUND AND SHALL BE CORRECTED WITH IN 30 DAYS. A COPY OF THE REPAIR MANIFEST SHALL BE FORWARDED TO THIS OFFICE. 1) THE FIRE ALARM HORN STROBES DID NOT FUNCTION DURING THE FLOW TEST 2) BATTERIES AT THE FIRE ALARM PANEL THAT HAVE CORRODED TERMINALS SHALL BE CHANGED OUT 3) R C I SYSTEMS, THE INSPECTING COMPANY, ALSO REPORTED A POSSIBLE OVERLOAD ON ALARM CIRCUIT #1. THIS SHALL BE REPAIRED |