Case: T09FR01212

Parcel: 124040760


Addresses:

1509 E 2ND ST

Inspection Status: Approved

Inspection History: INSP - LIFE SAFETY

Date Description Inspector Results Comments
05/11/2009 INSP - LIFE SAFETY Approved
04/08/2009 INSP - LIFE SAFETY Violation 1028.6 Emergency escape openings. Required emergency
escape openings shall be maintained in accordance with the
code in effect at the time of construction, and the following:
Required emergency escape and rescue openings shall be operational
from the inside of the room without the use of keys or
tools. Bars, grilles, grates or similar devices are allowed to be
placed over emergency escape and rescue openings provided
the minimum net clear opening size complies with the code that
was in effect at the time of construction and such devices shall
be releasable or removable from the inside without the use of a
key, tool or force greater than that which is required for normal
operation of the escape and rescue opening.
1026.1 General. In addition to the means of egress required by
this chapter, provisions shall be made for emergency escape
and rescue in Group R and I-1 occupancies. Basements and
sleeping rooms below the fourth story above grade plane shall
have at least one exterior emergency escape and rescue opening
in accordance with this section. Where basements contain one
or more sleeping rooms, emergency egress and rescue openings
shall be required in each sleeping room, but shall not be
required in adjoining areas of the basement. Such openings
shall open directly into a public way or to a yard or court that
opens to a public way.

____All windows in bedrooms must be operational from the inside of the room. Currently alot of the windows are sealed shut.