Inspection History Details
Inspection Status: Approved
Inspection History: VIOL - FLAMMABLE LIQUIDS
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/28/2009 | VIOL - FLAMMABLE LIQUIDS | Approved | ||
| 04/07/2009 | VIOL - FLAMMABLE LIQUIDS | Correction Required | 3404.2.7.4 Emergency venting. Stationary, above-ground tanks shall be equipped with additional venting that will relieve excessive internal pressure caused by exposure to fires. " Emergency venting must be installed. The vents must be the appropriate size for the tank. The tank manufacturer determines the size of vent required and the volume of venting required. |
|
| 04/07/2009 | VIOL - FLAMMABLE LIQUIDS | Correction Required | 3404.2.7.3.2 Vent-line flame arresters and venting devices. Vent-line flame arresters and venting devices shall be installed in accordance with their listings. Use of flame arresters in piping systems shall be in accordance with API 2028. " All oil tanks must be equipped with atmospheric vents and spark arrestors. |