Case: T09FR01188

Parcel: 131092340


Addresses:

1829 S CRAYCROFT RD

Inspection Status: Approved

Inspection History: VIOL - FLAMMABLE LIQUIDS

Date Description Inspector Results Comments
05/28/2009 VIOL - FLAMMABLE LIQUIDS Approved
04/07/2009 VIOL - FLAMMABLE LIQUIDS Correction Required 3404.2.7.4 Emergency venting. Stationary, above-ground tanks shall be equipped with additional venting that will relieve excessive internal pressure caused by exposure to fires.

" Emergency venting must be installed. The vents must be the appropriate size for the tank. The tank manufacturer determines the size of vent required and the volume of venting required.
04/07/2009 VIOL - FLAMMABLE LIQUIDS Correction Required 3404.2.7.3.2 Vent-line flame arresters and venting devices. Vent-line flame arresters and venting devices shall be installed in accordance with their listings. Use of flame arresters in piping systems shall be in accordance with API 2028.

" All oil tanks must be equipped with atmospheric vents and spark arrestors.