Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Case: T09FR01181

Parcel: 10511061R


Addresses:

4500 N ORACLE RD


Inspection Status: Correction Required

Inspection History: VIOL - PRECAUTION AGAINST FIRE

Case Number - T09FR01181

Inspection Description - VIOL - PRECAUTION AGAINST FIRE

Inspection Status - Correction Required

Date Description Inspector Results Comments
04/07/2009 VIOL - PRECAUTION AGAINST FIRE Correction Required 315.2.1 Ceiling clearance
Storage shall be maintained 2 feet or more below the ceiling in non-sprinklered areas of buildings or a minimum of 18 inches below sprinkler head deflectors in sprinklered areas of a building.

_____ Maintain the proper ceiling clearance according to code. Lower your stock to comply with the code.