Case: T09FR01163

Parcel: 12002034B


Addresses:

625 W AJO WY

Inspection Status: Violation

Inspection History: VIOL - FIRE PROTECTION SYSTEMS

Date Description Inspector Results Comments
04/07/2009 VIOL - FIRE PROTECTION SYSTEMS Violation 904.5.1 System test. Systems shall be inspected and tested for proper operation at 6-month intervals. Tests shall include a check of the detection system, alarms and releasing devices, including manual stations and other associated equipment.
___Provide up to date documentation of hood extinguishing system test.
04/07/2009 VIOL - FIRE PROTECTION SYSTEMS Violation 906.2 General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10.
_____ Extinguishers shall be inspected by occupant monthly and professionally serviced annually. A tag
shall be affixed to the extinguisher with records of these activities
04/07/2009 VIOL - FIRE PROTECTION SYSTEMS Violation 906.7 - Hangers and brackets. Hand-held portable fire extinguishers, not housed in cabinets, shall be installed on the hangers or brackets supplied. Hangers or brackets shall be securely anchored to the mounting surface in accordance with the manufacturer's installation instructions.