Inspection Status: Approved
Inspection History: INSP - FULL
Case Number - T09FR01162
Inspection Description - INSP - FULL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/07/2009 | INSP - FULL | Approved | ALL NOTED TFC VIOLATIONS HAVE BEEN CORRECTED. | |
04/07/2009 | INSP - FULL | Violation | 1.) TFC 901.6 AT PED'S NURSING STATION THE MISSING SPRINKLER HEAD ESCUTCHEON MUST BE REPLACED. | |
04/07/2009 | INSP - FULL | Violation | 2.) TFC 901.6 AT ENTRANCE TO ROOM #204 OF PED'S THE MISSING ESCUTCHEON MUST BE REPLACED. | |
04/07/2009 | INSP - FULL | Violation | 3.) TFC 901.6 OUTSIDE OF ROOM #208 OF PED'S THE MISSING ESCUTCHEON MUST BE REPLACED. | |
04/07/2009 | INSP - FULL | Violation | 4.) TFC 901.6 IN ROOM #207 OF PED'S THE MISSING ESCUTCHEON MUST BE REPLACED. | |
04/07/2009 | INSP - FULL | Violation | 5.) TFC 703.1.1 IN E.D., IN SOILED LINEN ROOM ACROSS FROM STAFF LOUNGE THE WALL PENETRATION MUST BE SEALED. | |
04/07/2009 | INSP - FULL | Violation | 6.) TFC 703.1.1 IN E.D. FAMILY CONSULTING ROOM, THE WALL PENETRATION BEHIND THE DOOR MUST BE SEALED. | |
04/07/2009 | INSP - FULL | Violation | 7.) TFC 703.1.1 IN THE GURNEY HALLWAY FROM THE HELI-PAD THE WALL PENETRATION MUST BE SEALED. | |
04/07/2009 | INSP - FULL | Violation | 8.) TFC 605.4.2 IN THE LIFE NET OFFICES AT THE END OF THE HALLWAY BOTH OFFICES HAVE ELECTRICAL POWER STRIPS "PIGGY BACKED" TOGETHER. EACH POWER STRIP SHALL BE PLUGGED DIRECTLY INTO AN OUTLET. |