Case: T09FR01161

Parcel: 11619359A

Inspection Status: Approved

Inspection History: INSP - FULL

Case Number - T09FR01161

Inspection Description - INSP - FULL

Inspection Status - Approved

Date Description Inspector Results Comments
09/17/2009 INSP - FULL Approved ALL NOTED TFC VIOLATIONS HAVE BEEN CORRECTED. APPROVED. 5 YEAR CHECK VALVE INSPECTION IS DUE. CHECK VALVE DONE PER T09FR02716.
08/17/2009 INSP - FULL Approved NOTED TFC VIOLATIONS HAVE BEEN CORRECTED EXCEPT THE SPRINKLER SYSTEM CHECK VALVE NEEDS 5 YEAR VISUAL INSP. ISSUED REPORT FOR CHECK VALVE INSP. REF: T090FR0
04/07/2009 INSP - FULL Violation 1.) TFC 605.6 IN ELECTRICAL ROOM THE OPEN WIRE SPLICE ON THE WEST WALL MUST BE ENCLOSED IN AN APPROVED JUNCTION BOX.
04/07/2009 INSP - FULL Violation 2.) TFC 605.4.3 IN ROOM #5 THE POWER CORD FOR THE POWER STRIP CANNOT BE ROUTED UNDER THE CLOSET DOOR.
04/07/2009 INSP - FULL Violation 3.) TFC 605.4.2 IN ROOM#4 THE POWER STRIPS ON THE SOUTH WALL MUST BE INDIVIDUALLY PLUGGED DIRECTLY INTO AN OUTLET AND CANNOT BE "PIGGY BACKED" TOGETHER.
04/07/2009 INSP - FULL Violation 4.) TFC 404.3.1 FIRE EVACUATION PLANS SHALL BE REVISED TO ADD REQUIREMENTS THAT EACH TEACHER MUST HAVE A KEY TO PLAYGROUND GATE IN THEIR POSSESSION DURING ALL FIRE DRILLS AND ACTUAL EMERGENCY EVACUATIONS.
04/07/2009 INSP - FULL Violation 5.) TFC 901.6.1 THE SPRINKLER SYSTEM CONTROL VALVE SHALL BE CHAINED AND LOCKED IN THE OPEN POSITION.
04/07/2009 INSP - FULL Violation 6.) TFC 510.1 BOTH DOORS PROVIDING ACCESS TO THE SPRINKLER SYSTEM CONTROL VALVE MUST HAVE A SIGN AFIXED ON THE EXTERIOR SIDE STATING "RISER ROOM" TO IDENTIFY THE LOCATION OF THE CONTROL VALVE. THE SIGN MUST BE CONSTRUCTED OF DURABLE MATERIAL, PERMANENTLY INSTALLED AND READILY VISIBLE.
04/07/2009 INSP - FULL Violation 7.) TFC 901.6.2 THE SPRINKLER SYSTEM ANNUAL INSPECTION REPORT SHALL BE SUBMITTED UPON RE-INSPECTION.
04/07/2009 INSP - FULL Violation 8.) TFC 506.1 AN APPROVED KEY BOX SHALL BE MOUNTED ON THE EXTERIOR OF THE BUILDING TO PROVIDE KEYS NECESSARY TO EMERGENCY RESPONDERS FOR ACCESS TO SPRINKLER SYSTEM CONTROL VALVE.