Inspection Status: Approved
Inspection History: INSP - FULL
| Date |
Description |
Inspector |
Results |
Comments |
| 09/17/2009 |
INSP - FULL |
|
Approved |
ALL NOTED TFC VIOLATIONS HAVE BEEN CORRECTED. APPROVED. 5 YEAR CHECK VALVE INSPECTION IS DUE. CHECK VALVE DONE PER T09FR02716. |
| 08/17/2009 |
INSP - FULL |
|
Approved |
NOTED TFC VIOLATIONS HAVE BEEN CORRECTED EXCEPT THE SPRINKLER SYSTEM CHECK VALVE NEEDS 5 YEAR VISUAL INSP. ISSUED REPORT FOR CHECK VALVE INSP. REF: T090FR0 |
| 04/07/2009 |
INSP - FULL |
|
Violation |
1.) TFC 605.6 IN ELECTRICAL ROOM THE OPEN WIRE SPLICE ON THE WEST WALL MUST BE ENCLOSED IN AN APPROVED JUNCTION BOX. |
| 04/07/2009 |
INSP - FULL |
|
Violation |
2.) TFC 605.4.3 IN ROOM #5 THE POWER CORD FOR THE POWER STRIP CANNOT BE ROUTED UNDER THE CLOSET DOOR. |
| 04/07/2009 |
INSP - FULL |
|
Violation |
3.) TFC 605.4.2 IN ROOM#4 THE POWER STRIPS ON THE SOUTH WALL MUST BE INDIVIDUALLY PLUGGED DIRECTLY INTO AN OUTLET AND CANNOT BE "PIGGY BACKED" TOGETHER. |
| 04/07/2009 |
INSP - FULL |
|
Violation |
4.) TFC 404.3.1 FIRE EVACUATION PLANS SHALL BE REVISED TO ADD REQUIREMENTS THAT EACH TEACHER MUST HAVE A KEY TO PLAYGROUND GATE IN THEIR POSSESSION DURING ALL FIRE DRILLS AND ACTUAL EMERGENCY EVACUATIONS. |
| 04/07/2009 |
INSP - FULL |
|
Violation |
5.) TFC 901.6.1 THE SPRINKLER SYSTEM CONTROL VALVE SHALL BE CHAINED AND LOCKED IN THE OPEN POSITION. |
| 04/07/2009 |
INSP - FULL |
|
Violation |
6.) TFC 510.1 BOTH DOORS PROVIDING ACCESS TO THE SPRINKLER SYSTEM CONTROL VALVE MUST HAVE A SIGN AFIXED ON THE EXTERIOR SIDE STATING "RISER ROOM" TO IDENTIFY THE LOCATION OF THE CONTROL VALVE. THE SIGN MUST BE CONSTRUCTED OF DURABLE MATERIAL, PERMANENTLY INSTALLED AND READILY VISIBLE. |
| 04/07/2009 |
INSP - FULL |
|
Violation |
7.) TFC 901.6.2 THE SPRINKLER SYSTEM ANNUAL INSPECTION REPORT SHALL BE SUBMITTED UPON RE-INSPECTION. |
| 04/07/2009 |
INSP - FULL |
|
Violation |
8.) TFC 506.1 AN APPROVED KEY BOX SHALL BE MOUNTED ON THE EXTERIOR OF THE BUILDING TO PROVIDE KEYS NECESSARY TO EMERGENCY RESPONDERS FOR ACCESS TO SPRINKLER SYSTEM CONTROL VALVE. |