Case: T09FR01149

Parcel: 11711080B


Addresses:

125 E PENNINGTON ST

Inspection Status: Correction Required

Inspection History: VIOL - FIRE PROTECTION SYSTEMS

Date Description Inspector Results Comments
04/03/2009 VIOL - FIRE PROTECTION SYSTEMS Correction Required IFC 903.3.3 Obstructed locations. Automatic sprinklers shall
be installed with due regard to obstructions that will delay
activation or obstruct the water distribution pattern. Automatic
sprinklers shall be installed in or under covered
kiosks, displays, booths, concession stands, or equipment
that exceeds 4 feet (1219 mm) in width.

_____1. Remove the drum riser platform or install an automatic sprinkler head under it for proper sprinikler coverage.


________________________________________________
(John E. Bieg, Fire Inspector, Tucson Fire Department)

I, ______________________ have received a copy of this inspection report. (Building Representative)


______________________________
(Captain)


Re-inspection scheduled on or after _____/_____/_____
Call Inspector Bieg at 235-4785 or 791-4502, if you have any further questions.


All noted Tucson Fire Code violations have been corrected: _____/_____/_____

______________________
John E. Bieg