Inspection Status: Correction Required
Inspection History: VIOL - BUILDING SVCS & SYSTEMS
Case Number - T09FR01136
Inspection Description - VIOL - BUILDING SVCS & SYSTEMS
Inspection Status - Correction Required
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/03/2009 | VIOL - BUILDING SVCS & SYSTEMS | Correction Required | 605.1 Abatement of electrical hazards. Identified electrical hazards shall be abated. Identified hazardous electrical conditions in permanent wiring shall be brought to the attention of the code official responsible for enforcement of the ICC Electrical Code. Electrical wiring, devices, appliances and other equipment that is modified or damaged and constitutes an electrical shock or fire hazard shall not be used. _____ Remove the breaker inhibiters from your electrical box as they prevent the box from breaking properly and are deemed an electrical hazard 605.3 Working space and clearance A working space of not less than 30 inches in width, 36 inches in depth, and 78 inches in height shall be provided in front of electrical service equipment. Where the service equipment is wider than 30 inches, working space shall be no less than the width of the equipment. No storage of any kind shall be located within the designated working space. **** Be sure to keep all electrical equipment clear of any combustable material and maintain proper working space around all electrical equipment*** |