Case: T09FR01135

Parcel: 11711080B


Addresses:

125 E PENNINGTON ST

Inspection Status: Correction Required

Inspection History: VIOL - INT.FINISH, DEC. MATL'S

Date Description Inspector Results Comments
04/03/2009 VIOL - INT.FINISH, DEC. MATL'S Correction Required IFC 807.1 General requirements. In occupancies in Groups A, E,
I and R-1 and dormitories in Group R-2, curtains, draperies,
hangings and other decorative materials suspended from walls
or ceilings shall meet the flame propagation performance criteria
of NFPA 701 in accordance with Section 806.2 or be
noncombustible.

_____1. All the acustic material hanging from the walls and ceiling located in the up stairs studio and iso storage shall be removed or treated to meet the flame propagation criteria of NFPA 701 in accordance with section 806.2