Inspection History Details
Inspection Status: Violation
Inspection History: INSP - FULL
Case Number - T09FR01130
Inspection Description - INSP - FULL
Inspection Status - Violation
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/02/2009 | INSP - FULL | Violation | 1. TFC 901.6.1 Control valve for sprinkler system needs to be secured/supervised to protect against tampering. | |
| 04/02/2009 | INSP - FULL | Violation | 2. TFC 901.6 Room C-5 sprinkler system must be maintained. Sprinkler head pipe needs to be sealed. | |
| 04/02/2009 | INSP - FULL | Violation | 3. TFC 1027.3 Room C2 Director's office- Exit sign needs repair/service. | |
| 04/02/2009 | INSP - FULL | Violation | 4. TFC 906.7 Room C2 Director's office- Portable fire extinguisher shall be mounted on wall or removed. | |
| 04/02/2009 | INSP - FULL | Violation | 5. TFC 605.1 Electrical hazards shall be abated. Electrical box cover 4" by 4" in front of kitchen needs a cover. | |
| 04/02/2009 | INSP - FULL | Violation | 6. TFC 605.1 Electrical hazards shall be abated. Dining room ceiling electrical box needs cover. |