Case: T09FR01130

Parcel: 12501001A


Addresses:

2700 E SPEEDWAY BL


Inspection Status: Violation

Inspection History: INSP - FULL

Case Number - T09FR01130

Inspection Description - INSP - FULL

Inspection Status - Violation

Date Description Inspector Results Comments
04/02/2009 INSP - FULL Violation 1. TFC 901.6.1 Control valve for sprinkler system needs to be secured/supervised to protect against tampering.
04/02/2009 INSP - FULL Violation 2. TFC 901.6 Room C-5 sprinkler system must be maintained. Sprinkler head pipe needs to be sealed.
04/02/2009 INSP - FULL Violation 3. TFC 1027.3 Room C2 Director's office- Exit sign needs repair/service.
04/02/2009 INSP - FULL Violation 4. TFC 906.7 Room C2 Director's office- Portable fire extinguisher shall be mounted on wall or removed.
04/02/2009 INSP - FULL Violation 5. TFC 605.1 Electrical hazards shall be abated. Electrical box cover 4" by 4" in front of kitchen needs a cover.
04/02/2009 INSP - FULL Violation 6. TFC 605.1 Electrical hazards shall be abated. Dining room ceiling electrical box needs cover.