Inspection History Details
Inspection Status: Approved
Inspection History: INSP - FULL
Case Number - T09FR01117
Inspection Description - INSP - FULL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/22/2009 | INSP - FULL | Approved | Noted violations have been corrected. | |
04/01/2009 | INSP - FULL | Violation | 1. TFC 1027.5 Emergency Exit Light in basement must be serviced/repaired. | |
04/01/2009 | INSP - FULL | Violation | 2. TFC 605.3 Outdoor maintenance room electrical box shall provide not less then 30 inches of clearance in front of electrical service box. | |
04/01/2009 | INSP - FULL | Violation | 3. TFC 510.1 Riser room must have an approved sign. It must be a durable material, permanently installed, readily visible. | |
04/01/2009 | INSP - FULL | Violation | 4. TFC 2701.3.3.6 Flammable liquids must be stored/contained in flammable storage cabinet. | |
04/01/2009 | INSP - FULL | Violation | 5. TFC 605.5 Extension cords (2 ea) in conference room shall not substitute for permanent wireing. | |
04/01/2009 | INSP - FULL | Violation | 6. TFC 605.1 Two power relocatable taps shall be provided in maintenance shop (east wall). Identified electrical hazards shall be abated. |