Case: T09FR01117

Parcel: 11504343A


Addresses:

1101 N 4TH AV


Inspection Status: Approved

Inspection History: INSP - FULL

Case Number - T09FR01117

Inspection Description - INSP - FULL

Inspection Status - Approved

Date Description Inspector Results Comments
07/22/2009 INSP - FULL Approved Noted violations have been corrected.
04/01/2009 INSP - FULL Violation 1. TFC 1027.5 Emergency Exit Light in basement must be serviced/repaired.
04/01/2009 INSP - FULL Violation 2. TFC 605.3 Outdoor maintenance room electrical box shall provide not less then 30 inches of clearance in front of electrical service box.
04/01/2009 INSP - FULL Violation 3. TFC 510.1 Riser room must have an approved sign. It must be a durable material, permanently installed, readily visible.
04/01/2009 INSP - FULL Violation 4. TFC 2701.3.3.6 Flammable liquids must be stored/contained in flammable storage cabinet.
04/01/2009 INSP - FULL Violation 5. TFC 605.5 Extension cords (2 ea) in conference room shall not substitute for permanent wireing.
04/01/2009 INSP - FULL Violation 6. TFC 605.1 Two power relocatable taps shall be provided in maintenance shop (east wall). Identified electrical hazards shall be abated.