Inspection Status: Approved
Inspection History: INSP - FULL
| Date |
Description |
Inspector |
Results |
Comments |
| 07/22/2009 |
INSP - FULL |
|
Approved |
Noted violations have been corrected. |
| 04/01/2009 |
INSP - FULL |
|
Violation |
1. TFC 1027.5 Emergency Exit Light in basement must be serviced/repaired. |
| 04/01/2009 |
INSP - FULL |
|
Violation |
2. TFC 605.3 Outdoor maintenance room electrical box shall provide not less then 30 inches of clearance in front of electrical service box. |
| 04/01/2009 |
INSP - FULL |
|
Violation |
3. TFC 510.1 Riser room must have an approved sign. It must be a durable material, permanently installed, readily visible. |
| 04/01/2009 |
INSP - FULL |
|
Violation |
4. TFC 2701.3.3.6 Flammable liquids must be stored/contained in flammable storage cabinet. |
| 04/01/2009 |
INSP - FULL |
|
Violation |
5. TFC 605.5 Extension cords (2 ea) in conference room shall not substitute for permanent wireing. |
| 04/01/2009 |
INSP - FULL |
|
Violation |
6. TFC 605.1 Two power relocatable taps shall be provided in maintenance shop (east wall). Identified electrical hazards shall be abated. |