Inspection History Details
Inspection Status: Approved
Inspection History: VIOL - FIRE PROTECTION SYSTEMS
Case Number - T09FR01116
Inspection Description - VIOL - FIRE PROTECTION SYSTEMS
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/03/2009 | VIOL - FIRE PROTECTION SYSTEMS | Approved | ||
04/01/2009 | VIOL - FIRE PROTECTION SYSTEMS | Violation | TFC 903.2.7 Group R. Existing sorority and fraternity house and existing Group R-4 occupancies shall have automatic sprinkler systems installed. A permit shall be issued within two years of the adoption of this code and the work shall be completed within three years of the adoption of this code. This ordinance took effect on October 23, 2007 and requires completion by October 22, 2010. ____Sprinkler system required by Oct. 22, 2010. Plans and permits required by Oct. 22 2009. |
|
04/01/2009 | VIOL - FIRE PROTECTION SYSTEMS | Violation | 904.11.5 Portable fire extinguishers for commercial cooking equipment. Portable fire extinguishers shall be provided within a 30-foot (9144 mm) travel distance of commercial-type cooking equipment. Cooking equipment involving vegetable or animal oils and fats shall be protected by a Class K rated portable extinguisher. ____Install/Mount one Class K extinguisher within 30ft of cooking equipment. |
|
04/01/2009 | VIOL - FIRE PROTECTION SYSTEMS | Violation | 906.1 Where required. 906.2 General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. ____All the extinguishers in the house, besides the class K in the kitchen, are not required by the Tucson Fire Department. If you wish to keep them, they need to be mounted and serviced annually. Check with your insurance company before removing them. |
|
04/01/2009 | VIOL - FIRE PROTECTION SYSTEMS | Violation | 907.2.10.1.2 Groups R-2, R-3, R-4 and I-1. Singleor multiple-station smoke alarms shall be installed and maintained in Groups R-2, R-3, R-4 and I-1 regardless of occupant load at all of the following locations: 1. On the ceiling or wall outside of each separate sleeping area in the immediate vicinity of bedrooms. 2. In each room used for sleeping purposes. 3. In each story within a dwelling unit, including basements but not including crawl spaces and uninhabitable attics. In dwellings or dwelling units with split levels and without an intervening door between the adjacent levels, a smoke alarm installed on the upper level shall suffice for the adjacent lower level provided that the lower level is less than one full story below the upper level. ____Smoke detectors required in every bedroom and room used for sleeping purposes. Also required in bedroom hallways. Smoke detector log included with this report. Complete and provide smoke detector log upon reinspection. |