Case: T09FR01109

Parcel: 124040760


Addresses:

1509 E 2ND ST

Inspection Status: Approved

Inspection History: VIOL - MEANS OF EGRESS

Date Description Inspector Results Comments
05/11/2009 VIOL - MEANS OF EGRESS Approved
03/31/2009 VIOL - MEANS OF EGRESS Violation 1008.1 Doors. Means of egress doors shall meet the requirements
of this section. Doors serving a means of egress system
shall meet the requirements of this section and Section 1017.2.
Doors provided for egress purposes in numbers greater than
required by this code shall meet the requirements of this section.

1008.1.8 Door operations. Except as specifically permitted
by this section egress doors shall be readily openable from
the egress side without the use of a key or special knowledge
or effort.

1008.2 Gates. Gates serving the means of egress system shall
comply with the requirements of this section. Gates used as a
component in a means of egress shall conform to the applicable
requirements for doors.

____Both gates serving the means of egress on the east side of building must swing open properly. They must also be openable from the egress side without the use of a key or special knowledge. They are currently pad locked.
____Remove keyed lock from kitchen door. Replace with a thumbturn lock.
____Remove keyed lock from "green room" door. Replace with thumbturn lock.
03/31/2009 VIOL - MEANS OF EGRESS Violation 1027.3 Exit sign illumination.

____Install both missing exit signs from courtyard. Both have been damaged/removed and currently have exposed electrical wires.
03/31/2009 VIOL - MEANS OF EGRESS Violation 1027.5 Illumination emergency power. The power supply for
means of egress illumination shall normally be provided by the
premises’ electrical supply. In the event of power supply failure,
illumination shall be automatically provided from an
emergency system for the following occupancies where such
occupancies require two or more means of egress:
1. Group A having 50 or more occupants.

____Install an emergency lighting unit in the chapter room.