Case: T09FR01109

Parcel: 124040760


Addresses:

1509 E 2ND ST

Inspection Status: Approved

Inspection History: VIOL - FIRE PROTECTION SYSTEMS

Date Description Inspector Results Comments
05/11/2009 VIOL - FIRE PROTECTION SYSTEMS Approved
03/31/2009 VIOL - FIRE PROTECTION SYSTEMS Violation 906.2 General requirements. Portable fire extinguishers shall
be selected, installed and maintained in accordance with this
section and NFPA 10.

____The Class K extinguisher in the kitchen needs an annual service/inspection. Service and tag the extinguisher.
03/31/2009 VIOL - FIRE PROTECTION SYSTEMS Violation TFC 903.2.7 Group R. Existing sorority and fraternity house and existing Group R-4 occupancies shall have automatic sprinkler systems installed. A permit shall be issued within two years of the adoption of this code and the work shall be completed within three years of the adoption of this code.
This ordinance took effect on October 23, 2007 and requires completion by October 22, 2010.

____Permits and plans required by Oct. 22, 2009. Complete system needs to be finalized by Oct. 22, 2010. The official "sprinkler letter" explaining the ordinance and sprinkler contractor list is included with this report.
03/31/2009 VIOL - FIRE PROTECTION SYSTEMS Violation 907.2.10.1.2 Groups R-2, R-3, R-4 and I-1. Singleor
multiple-station smoke alarms shall be installed
and maintained in Groups R-2, R-3, R-4 and I-1
regardless of occupant load at all of the following
locations:
In each room used for sleeping purposes.

____Test every smoke detector in every bedroom and room used for sleeping purposes. Fill out the smoke detector log provided and sign it. Provide the log on the re-inspection date.